AccreditationWhy emergency power

TYPE 1 & TYPE 3 EES For An ASC

TYPE 1 AND 3 EES POWER-SOURCE CLASSIFICATIONS FOR AN ASC

NFPA 99 refers to NFPA 111 and NFPA 110 when defining classification standards for backup or alternate power sources and generators. For our purposes:

  • Type 1 and Type 2 essential electrical systems correspond to a Type 10, Class X, Level 1 category under NFPA 110.
  • Type 3 essential electrical systems fall under Type 10, Class X, Level 2.

Understanding these components helps clarify their meaning:

Type

This indicates the maximum allowable power-transfer delay, measured in seconds. A Type 10 system means the transfer to backup power must occur within 10 seconds.

Class

This relates to the reserve runtime—the minimum number of hours the alternate source of power must be able to operate at its rated load without needing to be refueled or recharged. For Class X, no fixed runtime is specified. Instead, NFPA 110 and 111 note it as “other time in hours as required by the application, code, or user.”
In the case of an Ambulatory Surgery Center (ASC), this is generally left to the physicians to decide how long is necessary to complete a procedure safely.
However, accreditation underwriters often set their own minimum, which in most cases is 2 hours.

Level

NFPA 110 and 111 establish two levels:

Level 2 systems are used where a power outage would be less critical to patient safety or human life.

Level 1 systems are required where equipment failure could result in loss of life or serious injury.

Learn More About Battery Backup Power

To answer even more of your questions and find additional solutions to problems that could affect your medical facility or laboratory, check out these other articles from the EverSafe blog and the EverSafe Learning Center

Share this article

Further Reading

Why Healthcare Power Planning Shouldn’t Follow the Seasons
Healthcare ManagementVaccine Storage

Why Healthcare Power Planning Shouldn’t Follow the Seasons

On October 12, 2026, the U.S. Department of Energy issued an emergency order in response to elevated grid demand.

Read more
Case Study: Adapting a Two-Hour Backup Power Plan for a Dental Practice in Virginia 
Surgery Centers

Case Study: Adapting a Two-Hour Backup Power Plan for a Dental Practice in Virginia 

A dental practice in Virginia needed two hours of battery backup power for its operating room equipment.

Read more
Can One Battery Backup System Power Multiple Refrigerators and Freezers? 
Refrigerated Medications

Can One Battery Backup System Power Multiple Refrigerators and Freezers? 

Medi-Products can size a battery backup system to support multiple refrigerators, freezers, or other compatible devices, including equipment located in different rooms.

Read more