TYPE 1 AND 3 EES POWER SOURCE CLASSIFICATIONS FOR AN ASC

NFPA 99 refers to NFPA 111 and 110 to define the classifications of alternative power sources and generators.
Type 1 and 2 essential electrical systems consist of a Type 10, Class X, Level 1 System per NFPA 110 The system for a Type 3 essential electrical system is classified as a Type 10, Class X, Level 2. The following is what these Levels, classes and types are:

Type:
The Standby Power System type refers to the maximum interruption time that is permitted in seconds. This case being a Type 10 the maximum permitted transfer time is 10 seconds.

Class:
The Class is a reference to the reserve time, which is the minimum time in hours that the alternative power source is designed to run based on its rated load without having to be refueled or recharged. For Class X there is not a run-time listed. The NFPA 111 and 110 states “Other time in hours as required by the application, code or user” so therefore in the case of an Ambulatory Surgery Center we interpret that it would be up to the practicing physicians how much time they would need to complete their case.
Often the accreditation underwriter would have their own codified minimum time required, which in most cases is 2 hours.

Level:
NFPA 110 and 111 list 2 levels one and two
Level 1 Systems are necessary where there would be a risk of loss of life or serious injury to the patient if the equipment were to fail.
Level 2 Systems shall be installed where a power failure would be less critical to human life and safety.

To find out if your ASC or office based surgery center is required to have type 1 system you may refer to our NFPA TYPE 1 ESSENTIAL ELECTRICAL SYSTEMS AND AMBULATORY SURGERY CENTERS page.

Learn More About Battery Backup Power

To answer even more of your questions and find additional solutions to problems that could affect your medical facility or laboratory, check out these other articles from the Medi-Products blog and the Medi-Products Learning Center:

Surgery Room Design and Emergency Backup Power

Gasoline Powered Generators vs Battery Powered Generators for Medical Facilities

Battery Backup Costs For Office-based and Ambulatory Surgery Centers.

Share this article

Further Reading

Case Study: How Battery Backup Power Supports Continuous Operation of Critical Hemodialysis Equipment 
Case Study

Case Study: How Battery Backup Power Supports Continuous Operation of Critical Hemodialysis Equipment 

For an acute care hospital in Eastern Pennsylvania, preparing for a power outage meant looking beyond the equipment at the patient’s bedside. The hospital needed reliable backup power for its central reverse osmosis (RO) water purification system, an essential part of the infrastructure supporting hemodialysis.  The RO system was designed to meet stringent international medical […]

Read more
How Can Battery Backup Power Reduce Carbon Emissions in Healthcare?
Energy EfficiencyEngineering

How Can Battery Backup Power Reduce Carbon Emissions in Healthcare?

Battery backup protects essential equipment and temperature-sensitive inventory in healthcare facilities. It can also support sustainability goals, but the environmental benefit depends on the application. Batteries can help your facility reduce emissions through how they are charged, the generator operation they replace, and the waste they help prevent.

Read more
Flu Season Means Higher Stakes for Refrigeration
Healthcare StorageRefrigerated Medications

Flu Season Means Higher Stakes for Refrigeration

Flu season changes more than the number of patients walking through the door. For pharmacies, clinics, and outpatient facilities, it can also change how vaccine refrigeration equipment is used.

Read more